ANALYTICAL REPORT

S.N. : 6124
DATE IN : 8/05/92
DATE OUT : 8/25/92

 

CLIENT: Compotite Corp.

Material: ‘Composeal Gold’ Crack Isolation Waterproof Membrane, 40 Mil.

SUBMITTED FOR: ASTM D 4551 - 86b Test

1.0 Reference Procedure

1.1 Engineering Standard Methods #
1.2 EPA #
1.3 ASTM # D4551 - 86b

2.0 Test Results

The following tests were conducted as specified in ASTM D 4551-86b (Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic flexible Concealed Water- Containment Membrane).

 

PROPERTY UNIT STANDARD READING
Thickness inch 0.40, min 0.042
Tensile Strength 1bf/in. of width 80, min 86
Tensile Stress at 100% Elongation 1bf/in. of width 40, min 42
Elongation at break % 300, min 330
Tear Resistance 1bf/in. of width 250, min 257
Pinholes number none none
Micro-organism Resistance Specimen, pass/fail 12 of 12 pass 12 of 12 pass
Puncture Resistance Specimen, pass/fail 6 of 6 pass 6 of 6 pass
Indentation Resistance Specimen, pass/fail 3 of 3 pass 3 of 3 pass
Folding Resistance Specimen, pass/fail 3 of 3 pass 3 of 3 pass
Chemical Resistance
Distilled H2O %  Weight Change +1%, max. +0.030%
Soapy H2O %  Weight Change +2%, max. +0.097%
Alkali Specimen, pass/fail 3 of 3 pass 3 of 3 pass
Hydrostatic Pressure Test Specimen, pass/fail 3 of 3 pass 3 of 3 pass
Shrinkage % Original 5 %, max. 1.15 %
Volatile loss at 1580F % Loss 1.5 max. 0.08

 

As shown in our Test Report, it has passed ASTM D 4551 - 86b Test.

Report on sample by client applies only to sample. Report on sample by us applies only to lot sampled. Information contained herein is not to be used for reproduction except by special permission. Samples retained for thirty days maximum after date report unless specifically requested otherwise by client. The liability of the U.S. Analytical Laboratories with respect to the services charged for herein, shall in no exceed the amount of the invoice.

 

 

 

 

U.S. ANALYTICAL LABORATORIES
Analytical and Testing Service Member of A.S.T.M.
759 S. STATE COLLEGE BLVD., SUITE 6
FULLERTON, CALIF. 92631
TEL.714/ 773-9151                                                                     FAX.714/ 773-0521


 

Test Backgrounds :

Plastic Flexible Concealed Water-Containment Membrane Sampling:

25 Membranes were randomly Selected, Geometric Mean : 20

(ASTM D 1898 : Practice for Sampling of Plastics)

* No Production Lot Number was issued with this material.

Test Procedures:

Tests were performed in accordance with ASTM D 4551 - 86b, Sec. 11

Micro-organism Resistance Test : Basic Medium - Mixed Culture (Fungi) (ASTM D 874 - 84)

Test Results : No Color Change on Surface Characteristics by Visual Observation.
Physical Observation : No weight Change.

Hydrostatic Pressure Test:

Specimens : 3 Specimens of flat material 3 by 3 inch selected in accordance with ASTM D 4551, 12.1

Inner Dia. of the Pressure Tube : 2 inch

Outer Dia. of the Pressure Tube : 3 inch

Observations : Made observations at 10-min. intervals for the first hour, and at hourly intervals for the succeeding 7 hours, after which left the specimen under hydrostatic pressure for 40 hours and examined again. : No evidence of wetness on top of the material or the formation of a droplet found.

 

 

 